For a W.C. up to 50 metres horizontally from the soil stack. Do
not use where a vertical lift is required.

For a Saniflo installation the pipework
should not exceed 50 metres, and must incorporate a fall of at least
1 in 200 (1 inch per 15 feet along its length.
If the piperun is over 40 feet in
length, increase the pipe size to 32 mm (1.25") from that point
onwards. (Each bend reduces maximum pumping distance by about 1
metre).

The Saniflo unit is
positioned for connection to the WC pan spigot (see illustration
above) allowing adequate clearance for the unit to be removed for
maintenance. It may be necessary to mount the WC cistern on battens
in order to achieve this clearance.
The outlet socket is connected to 22 mm
diameter copper pipe to BS 2871 Part 1 1971 Specification for
copper and copper alloys. Tubes—Copper tubes for water, gas and
sanitation (or other pipework approved by the BBA for use with
the unit. This includes rigid solvent weld plastic pipework which
has a BS Kitemark or is BBA approved). Joints must be made with
fittings to BS 2051 Part 2 1984 Specification for olive type
copper alloy compression tube fittings.
All discharge pipework from the unit
should run horizontally with a slight fall (approximately 1 in 200
or 5 mm per metre run). Sharp bends should be avoided where
possible.
The internal vent pipe (supplied) must
be fitted to terminate above the level of the top of the WC pan .
Alternatively, if preferred, 22 mm diameter push fit ventilation
pipework can be fitted and run to the outside of the
building.
All pipework must be adequately
supported throughout its length as detailed in BS Code of Practice
310 1965 Water supply.
Electrical connection
The electrical supply cable from the
unit must be connected (with the mains supply switched off) to an
unswitched fused (5 amp) outlet, 240 V single phase domestic
supply |